In this short podcast episode, Bryan talks about what happens when you adjust the condenser airflow: you have the same charge, different numbers. This short covers HVAC condensers and flooded condensers in refrigeration applications.
When you increase condenser airflow by repairing a condenser fan or washing the unit, the pressure and subcooling readings change even though the charge stays the same. Refrigerant enters the condenser as superheated vapor and goes through three stages: desuperheating, condensing, and subcooling. The key thing to remember is that these three stages can occur at different points of the condenser as the operating conditions change.
Higher head pressure doesn't necessarily lead to higher subcooling, as subcooling depends on both saturation temperature and actual liquid temperature; if both change, head pressure can't tell us which way subcooling went. Exceptionally bad airflow across the condenser and high compression ratios can also interfere with liquid delivery. Uneven condenser airflow distribution also affects refrigerant distribution in the condenser. We shouldn't use low subcooling as an automatic indicator to add more charge.
If there's one thing to remember, it's that you need to fix the airflow problem before deciding there is a charge problem. Operating readings can change without the total refrigerant charge changing.